Eaton

Eaton Distribution parts

رقم القطعة: 106216

لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.

يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.

الوصف

Eaton Distribution parts

المواصفات

Ambient operating temperature - max40 °C
Ambient operating temperature - min-5 °C
Climatic proofingDamp heat, cyclic, to IEC 60068-2-30 Damp heat, constant, to IEC 60068-2-78
FunctionsUninterrupted operation (Control mode) Low-voltage h.b.c. switch-fuse unit
Special featuresContinuous operation (rated operating mode)Mounting with snap-on mechanismNH-fuse-links →#289998With clamp/screw connection setWith fuse monitoringWith connection area cover
Catalog Number106216
Model CodeNH-SLS-00/160-60-SI
Product Length/Depth610 mm
كل المواصفات (62)
Product Height136 mm
Product Width49 mm
Product Weight1.25 kg
CompliancesEN 60947-5-1 RoHS conform
CertificationsIEC/EN 60255 VDE 0435 Part 303
Source URLhttps://www.eaton.com/gb/en-gb/skuPage.106216.html
Suitable forTriple T profile Combi-base for busbar mounting (12 - 30 mm) x 5/10 mm Combi-base for direct busbar mounting Double T profile
Used with20 mm x 5/10 mm rail 12 mm x 5/10 mm rail Double T profile Triple T profile 25 mm x 5/10 mm rail 15 mm x 5/10 mm rail 30 mm x 5/10 mm rail Busbar fuse material 60 mm system
Type60 mm systemBusbar fuse material
Degree of protectionIP30 (operating state) IP10 (front cover open) IP30
ModelFuse switch disconnector
Mounting positionVertical or horizontal
Number of polesThree-pole
Voltage rating at AC230 V ACContacts: 250 V ACContacts: 500 / 400 V AC at AC-23BContacts: 690 V AC at AC-21BContacts: 690 V AC at AC-22BRelay contacts: 230 V AC at AC-15Relay contacts: 250 V AC
Rated uninterrupted current (Iu)160 A
Rated operation current (Ie)160 A
Voltage rating400 V AC
Terminal capacity (solid wire)2.5 mm² (2x) 2.5 mm² (2x) at box terminal
Terminal capacity (stranded cable)1.5 mm² - 70 mm² (1x) at box terminal 70 mm² (1x) at flange connection
Frequency rating50 Hz - 60 Hz
Pollution degree3
Admissible heat dissipation (NH-SE) - max12 W
Fuse current rating at 500 V - max160 A
Heat dissipation at Ith AC without NH-SE20 W
Operating altitude without derating - max2000 mm
Rated insulation voltage (Ui)400 V
Direction of incoming supplyAs required
Electrical connection type of main circuitRail connection
Overvoltage categoryIII
Frequency rating of contacts50 Hz - 60 Hz
Terminal capacity (cable)9 mm x 0.8 mm (6x) at box terminal
Frame00
Rated impulse withstand voltage (Uimp)4 kV
Lifespan, mechanical100000000 operations
Lifespan, electrical150000 operations
Rated conditional short-circuit current (Iq)50 kA 50 kA at AC (effective)
Construction size (fuse inserts)NH00
Rated operating voltage (Ue) at AC - max690 V
Rated operational current125 A / 160 A (AC-23B) 160 A (AC-21B) 1 A (230 V AC-15) 160 A (AC-22B)
Voltage range(0.8 - 1.1) x Ue
Screw diameter for flange connectionM8
Conventional thermal current Ith of auxiliary contacts (1-pole, open)4 A
Rated operational current (gL/gG) - max160 A
ConnectionTop or bottom
Distance between busbar centers60 mm
Release indicationMechanical top-plate indicator
Distance between rail centers60 mm
Permitted heat loss from fuse links - max20 W at 160 A
Terminal capacity (copper busbar)Max. 20 mm x 8 mm for flat busbar at flange connection
TerminalsLift terminals
Utilization categoryAC-15
Admissible back-up fuse - max4 A gL
Pick-up time - max500 ms
Power consumption per phase (rung)2 VA (L2/L3)

منتجات مشابهة

لوحات و توزيع

السعر عند الطلب

اطلب عرض سعر