MZX-e SLU1 Status Lamp Unit, Indication only English / Arabic
رقم القطعة: 508.033.002.EA
لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.
يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.
رقم القطعة: 508.033.002.EA
لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.
يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.
The MZX-e extinguishing control panel is powerful yet user-friendly and is designed and manufactured to a high standard. The panel features approval to BS EN 12094- 1:2003, BS EN 54-2 and 4 and is designed to BS 7273 part 1. The panel has extensive configuration options but is easy to install, programme and operate. The removable chassis enables the engineer to “first fix” an empty cabinet and then fit the chassis at the commissioning stage. There is a comprehensive range of accessories available to meet most customer requirements. Operation Three fully-monitored detection zones are provided. Zones 1 and 2 normally provide first stage and second stage fire conditions to allow extinguishant discharge (coincidence detection zones). Zone 3 is an auxiliary zone for detection only purposes. Zone 4 is used as a manual release zone. Facilities Three fully-monitored alarm circuits are provided, each rated at 0.5A with various configuration options via the engineers DIL switch settings. Two circuits are designed to provide audible warning of any fire condition and one circuit to provide an individually distinct audible warning of the pre-discharge, discharged and emergency hold condition. Two fully-monitored actuator/solenoid circuits, each rated at 1A, operate simultaneously upon “extinguishant release”. An RS485 multi-drop circuit link supports up to 7 Status Controller/Indicators of any type mixed on the communication path. Additional terminals and configuration options allows the engineer to configure the manual release, abort and hold switches to either data comms or hard wired inputs as required. Normally-open inputs provide for remote evacuate, silence alarms, system reset, lock-off input, low pressure and gas discharged pressure switch input. Outputs are provided for first stage signalling, second stage signalling, system discharged, common fire and common fault. These outputs may be configured as either Volt-Free C/O contacts or monitored 24 V (50 mA) outputs. A system reset Volt-Free relay is also provided.
| ZETTLER Order Code | 508.033.002.EA |
|---|---|
| ZETTLER Category | Control Panels, Repeaters & Displays |
| ZETTLER Model | MZX |
| ZETTLER Range | Centrali di estinzione e accessori |
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر
ZETTLER
اطلب عرض سعر