الوصف

جهاز حماية من الجهد العابر، فئة I OVR T1-T2 3N 100-255 P TS، رباعي الأقطاب

المواصفات

Product Net Width144 mm
Product Net Depth / Length73 mm
Product Net Height90 mm
Product Net Weight1.2 kg
Number of Auxiliary Contacts NO1
Number of Auxiliary Contacts NC1
Number of Poles4P
StandardsIEC 61643-11
كل المواصفات (63)
Width in Number of Modular Spacings8
Ambient Air TemperatureOperation -40 ... +70 °C
Maximum Operating Altitude PermissibleWithout Derating 2000 m
REACH Declaration9AKK107492A1906
RoHS Declaration9AKK108467A9302
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
WEEE B2C / B2BBusiness To Consumer
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
Declaration of Conformity - CE9AKK108467A9302
Package Level 1 Unitsbox 1 piece
Package Level 1 Gross Weight1.36 kg
ETIM 9EC001457 - Combined arrester for power supply systems
UNSPSC39-12-16-04
E-Number (Finland)3217683
E-Number (Norway)1629991
Source URLhttps://new.abb.com/products/2CTB812111R2300/ovr-t1-t2-3n-100-255-p-ts
ABB Taxonomy PathLow Voltage Products and Systems > Modular DIN Rail Products > Surge Protective Devices SPDs > Surge Protective Devices SPD Class I
ABB Classification IDs9AAC910006, 9AAC100511, 9AAC171944
SCIP3011d554-48f7-4f86-8cdb-df7f9143fd70 Germany
Short-Circuit Protective DevicesgG Type Fuses 315 A
ETIM 10EC001457 - Combined arrester for power supply systems
Dimension Diagram9AKK108467A9590
Rated Service Short-Circuit Breaking Capacity (Ics)100 kA
Number of Protected Poles4
Mounting TypeDIN-Rail
VersionPlug-in
REACH InformationFalse - does not contain substances > 0.1 mass percentage
RoHS Date20230322
REACH Date20231212
Frequency (f)45…65 Hz
Number of Batteries0
Declaration9AKK108467A9390
Voltage Protection Level ( Up)(L-N) 1.5 kV
Type of Low Voltage Distribution SystemTT
Nominal AC Voltage of the System (Uo)236 … 400 V
Maximum Continuous Operating Voltage (Uc)(L-PE) 264 V
Temporary Overvoltage Test Value (UT)(L-N) 440/120min V
Discharge CurrentNominal (8 / 20 µs) 25 kA
Impulse CurrentI (imp, 10 / 350 µs, L-N) 25 kA
Short Circuit Withstand Icc100 kA
Arrester ClassI
Number of Conductors5
Auxiliary Circuit LoadMinimum 75Vdc - 500mA
Status IndicatorYes
Cross-Section (A<subMaximum Conductor Solid-Stranded 50 mm²
Follow Current Extinction Capacity If (I fi)(L-N) 50 kA
Maximum Continuous Operating Voltage UL/CSA (MCOV)(L-PE) 255 V
Voltage Protection Rating UL/CSA (VPR)Lpe 4000 V
Type of Low Voltage Distribution System UL/CSAWye
Data Sheet, Technical Information9AKK108467A5402
Instructions and Manuals9AKK108467A8849
UL Certificate9AKK108466A2255
Mechanical Drawings9AKK108467A9590
VDE Certificate9AKK108468A0510
KEMA Certificate9AKK108468A0509

السعر عند الطلب