| Country of Origin | India |
|---|---|
| Product Net Width | 191 mm |
| Product Net Depth / Length | 193 mm |
| Product Net Height | 230 mm |
| Product Net Weight | 4.79 kg |
| Number of Poles | 2P |
| Standards | IEC 60947-3 |
| Rated Operational Voltage | Main Circuit 690 V AC |
| Rated Short-time Withstand Current Low Voltage (Icw) | for 1 s 14 kiloampere rms |
|---|---|
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 12 kV |
| Power Loss | at Rated Operating Conditions per Pole 36 W |
| Degree of Protection | acc. to IEC 60529 IP20 |
| Tightening Torque | 30 ... 44 N·m |
| Terminal Type | Lug terminals |
| Pollution Degree | 3 |
| REACH Declaration | 1SCC011021D0201 |
| RoHS Declaration | 1SCC011020D0201 |
| RoHS Information | Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019 |
| Toxic Substances Control Act - TSCA | 1SCC011025D0201 |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| ABB Site Meeting Group Waste To Landfill Target | UL 2799 Zero Waste To Landfill Validation available |
| Environmental Product Declaration - EPD | 1SCC311198D0201 |
| Declaration of Conformity - CE | 1SCC311099D2704 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Width | 240 mm |
| Package Level 1 Depth / Length | 270 mm |
| Package Level 1 Height | 206 mm |
| Package Level 1 Gross Weight | 5.4 kg |
| Package Level 1 EAN | 6417019273587 |
| Object Classification Code | Q |
| ETIM 9 | EC001040 - Fuse switch disconnector |
| eClass | V11.1 : 27371401 |
| UNSPSC | 39122233 |
| IDEA Granular Category Code (IGCC) | 5291 >> Fuse switch disconnector |
| Source URL | https://new.abb.com/products/1SCA022811R2740/os400d02p |
| ABB Taxonomy Path | Low Voltage Products and Systems > Switches > Switch Fuses |
| ABB Classification IDs | 9AAC910006, 9AAC100791, 9AAC210947 |
| Conventional Free-air Thermal Current (Ith) | Θ = 40 °C 400 A |
| ETIM 10 | EC001040 - Fuse switch disconnector |
| Country of Origin (CountryOfOrigin) | Finland |
| Conventional Thermal Current (Ithe) | Fully Enclosed 400 A |
| Handle Type | Pistol |
| Fuse Size | NH0 |
| Fuse System | DIN |
| Rated Current (In) | Main Circuit 400 A |
| Mounting Type | Base mounting |
| Operating Mode | Front |
| Position of Line Terminals | Top In - Bottom Out, Bottom In - Top Out |
| Rated Conditional Short-Circuit Current (Inc) | (500 V) 100 kA |
| Rated Operational Current AC-21A (Ie) | (500 V) 400 A |
| Rated Operational Current AC-22A (Ie) | (380 ... 415 V) 400 A |
| Rated Operational Current AC-23A (Ie) | (380 ... 415 V) 400 A |
| Rated Operational Power AC-23A (Pe) | (220 ... 240 V) 132 kW |
| Switches Operating Mechanism | 02 (Left Side) |
| Terminal Width | 25 mm |
| Data Sheet, Technical Information | 1SCC311013C0201 |
| Instructions and Manuals | 1SCC311015M0215 |
| End Of Life Disassembling Instructions | 1SCC311050M0201 |
| A2L Certificate – IEC | 1SCC311209D0201 |
| CCC Certificate | CCC OS315-400 2016 |
| UL Certificate | No certification needed |
| DNV GL Certificate | 1SCC311131D0203 |
| ATEX Certificate | No certification needed |
| Mechanical Drawings | OS400D02.igs |