DS-ARC1 M C10 A30
رقم القطعة: 2CSA275103R1104
لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.
يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.
رقم القطعة: 2CSA275103R1104
لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.
يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.
جهاز كشف القوس الكهربائي بحماية التيار المتبقي DS-ARC1 M C10 A30، أحادي القطب
| EPLAN Data | 9AAC190691_EPLAN |
|---|---|
| Product Net Width | 52.5 mm |
| Product Net Depth / Length | 69 mm |
| Product Net Height | 85 mm |
| Product Net Weight | 240 g |
| Number of Poles | 1P+N |
| Standards | IEC/EN 62606 |
| Rated Operational Voltage | 230...240 V AC |
| Rated Frequency (f) | 50 … 60 Hz |
|---|---|
| Rated Insulation Voltage (Ui) | 500 V |
| Rated Impulse Withstand Voltage (Uimp) | 4 kV |
| Power Loss | Total 1.8 W |
| Wire Stripping Length | 12 mm |
| Degree of Protection | Terminals IP20 |
| Tightening Torque | 2.8 N·m |
| Terminal Type | Screw Terminals |
| Width in Number of Modular Spacings | 3 |
| Ambient Air Temperature | Operation -25 ... 55 °C |
| Resistance to Shock acc. to IEC 60068-2-27 | 30g 2 shocks 13 ms |
| Pollution Degree | 2 |
| REACH Declaration | 9AKK108467A9482 |
| RoHS Declaration | 9AKK107046A6530 |
| RoHS Information | Following EU Directive 2011/65/EU |
| WEEE B2C / B2B | Business To Consumer |
| WEEE Category | 5. Small Equipment (No External Dimension More Than 50 cm) |
| Environmental Product Declaration - EPD | 9AKK108470A1707 |
| Declaration of Conformity - CE | 9AKK107046A6529 |
| Package Level 1 Units | box 1 piece |
| Package Level 1 Gross Weight | 0.270 kg |
| Object Classification Code | F |
| ETIM 9 | EC002695 - Earth leakage circuit breaker with auxiliary device |
| eClass | V11.0 : 27142213 |
| E-Number (Finland) | 3211125 |
| E-Number (Norway) | 1683225 |
| Source URL | https://new.abb.com/products/2CSA275103R1104/ds-arc1-m-c10-a30 |
| ABB Taxonomy Path | Low Voltage Products and Systems > Modular DIN Rail Products > Protection Against Arc Faults AFDDs > Arc Fault Detection Devices with Integrated Overcurrent and Residual Current Protection - AFDD+RCBO |
| ABB Classification IDs | 9AAC910006, 9AAC190690, 9AAC190691 |
| SCIP | 0a4c182f-9cbd-4163-92db-03c9c44f6806 Italy |
| Resistance to Vibrations | 20 Cycles with Load 0.8 In: 5g or 0.2mm 5 … 150 Hz |
| ETIM 10 | EC002695 - Earth leakage circuit breaker with auxiliary device |
| Mounting Position | Any |
| Dimension Diagram | 9AKK107046A6174 |
| Contact Position Indication | Red ON / Green OFF |
| Rated Service Short-Circuit Breaking Capacity (Ics) | 7.5 kA |
| Rated Ultimate Short-Circuit Breaking Capacity (Icu) | 10 kA |
| Number of Protected Poles | 1 |
| Rated Current (In) | 10 A |
| Mounting Type | DIN-Rail |
| Connecting Capacity | Busbar 10 mm² |
| REACH Information | True - contains substances > 0.1 mass percentage |
| RoHS Date | 20180903 |
| REACH Date | 20240429 |
| Accessory Type | Auxiliary contact |
| Accessories Available | Yes |
| Number of Modules | 3 |
| Built-In Depth (t2) | 69 mm |
| Overvoltage Category | III |
| Electrical Endurance | 10000 cycle |
| Mechanical Endurance | 20000 cycle |
| Screw Terminal Type | Failsafe Bi-directional Cylinder-lift Terminal |
| Actuator Type | Toggle |
| Environmental Conditions | 28 cycles |
| Type of Residual Current | Type A |
| Dielectric Test Voltage | 2.5 kV |
| Rated Residual Current | 30 mA |
| Input Voltage Type | AC |
| Number of Batteries | 0 |
| Carbon Footprint (Full Lifecycle) | 20.8436 kg CO₂ eq |
| Rated Short-Circuit Capacity | 10 kA |
| Energy Limiting Class | 3 |
| Tripping Characteristic | C |
| Power Supply Connection | Arbitrary |
| Reference Ambient Air Temperature | 30 °C |
| Test Voltage (Ut) | 170 … 264 V |
| Rated Residual Breaking Capacity (IΔm) | 6 kA |
| Number of Modular Spacings per DIN Rail | 3 |
| Fault Indication | Blue Flag on Toggle |
| Operating Characteristic | Instantaneous |
| Position of Neutral Terminals | Right |
| Housing Type | Insulation group I, RAL 7035 |
| Mounting Position of Accessories | Right |
| Data Sheet, Technical Information | 9AKK107046A7200 |
| Instructions and Manuals | 9AKK107046A6173 |
| Mechanical Drawings | 9AKK107046A6174 |
| VDE Certificate | 9AKK107046A6968 |