ABB

S201-C40

رقم القطعة: 2CDS251001R0404

لا يعرض أي بائع سعرًا لهذا المنتج بعد. أرسل طلبك وسنعود إليك بأفضل عرض.

يكتمل الطلب في تطبيق Ohmva بعد تسجيل الدخول.

الوصف

قاطع دائرة مصغر S201-C40، أحادي القطب

المواصفات

Country of OriginCzechia
EPLAN Data9AAC204436_EPLAN
Product Net Width17.5 mm
Product Net Depth / Length69 mm
Product Net Height88 mm
Product Net Weight0.12 kg
Number of Poles1P
StandardsIEC/EN 60898-1
كل المواصفات (118)
Rated Operational Voltageacc. to IEC 60898-1 230 V AC
Rated Frequency (f)50 / 60 Hz
Rated Insulation Voltage (Ui)acc. to IEC/EN 60664-1 440 V
Rated Impulse Withstand Voltage (Uimp)4 kV
Power Loss4.8 W
Mounting on DIN RailTH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
Wire Stripping Length12.5 mm
Degree of ProtectionIP20
Recommended Screw DriverPozidriv 2
Tightening Torque2.8 N·m
Terminal TypeScrew Terminals
Width in Number of Modular Spacings1
Maximum Operating Voltage UL/CSA60 V DC
Tightening Torque UL/CSA18 in·lb
Ambient Air TemperatureOperation -25 ... +55 °C
Resistance to Shock acc. to IEC 60068-2-2725g 2 shocks 13 ms
Pollution Degree3
REACH Declaration9AKK107492A1906
RoHS Declaration9AKK108472A0372
RoHS InformationFollowing EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA9AKK108468A8104
WEEE B2C / B2BBusiness To Business
WEEE Category5. Small Equipment (No External Dimension More Than 50 cm)
ABB Site Meeting Group Waste To Landfill TargetNo non-hazardous waste is sent to a landfill
EcoSolutions Profile9AKK108469A3796
Environmental Product Declaration - EPD9AKK108472A3863
Recyclability Rate of the Product acc. to EN45555Design for Closing Resource Loops - Standard EN45555 - 80.7 %
Declaration of Conformity - CE2CDK403001D0607
Declaration of Conformity - UKCA9AKK108467A5053
Package Level 1 Unitscarton 10 piece
Package Level 1 Gross Weight1.24 kg
Object Classification CodeF
ETIM 9EC000042 - Miniature circuit breaker (MCB)
eClassV11.0 : 27141901
UNSPSC39121603
IDEA Granular Category Code (IGCC)4897 >> Miniature circuit breakers
E-Number (Finland)3210440
E-Number (Norway)1664845
E-Number (Sweden)2100528
Source URLhttps://new.abb.com/products/2CDS251001R0404/s201-c40
ABB Taxonomy PathLow Voltage Products and Systems > Modular DIN Rail Products > Miniature Circuit Breakers MCBs > Miniature Circuit Breakers MCBs > S200
ABB Classification IDs9AAC910006, 9AAC720001, 9AAC100489, 9AAF400065, 9AAC204436, 9AAF622810, 9AAF626992
Resistance to Vibrations20 Cycles with Load 0.8 In: 5g 5 ... 150 ... 5 Hz
ETIM 10EC000042 - Miniature circuit breaker (MCB)
Lead Time0 day
Mounting Positionany
Country of Origin (CountryOfOrigin_PUBRABB008)Czechia
Lead Time (LeadTime_PUBRABB008)0 day
Made To Order (MadeToOrder_PUBRABB008)No
Warranty Return (NoWarrantyReturn_PUBRABB008)Product under warranty must be returned
Product Sales Status (ProductSalesStatus_PUBRABB008)Active
Quote Only (QuoteOnly_PUBRABB008)No
Stocked At Warehouses (StockedAtWarehouses_PUBRABB008)BRABB008EXPU
Country of Origin (CountryOfOrigin_PUCHSEC006)Czechia
Lead Time (LeadTime_PUCHSEC006)0 day
Made To Order (MadeToOrder_PUCHSEC006)No
Warranty Return (NoWarrantyReturn_PUCHSEC006)Product under warranty must be returned
Product Sales Status (ProductSalesStatus_PUCHSEC006)Active
Quote Only (QuoteOnly_PUCHSEC006)No
Stocked At Warehouses (StockedAtWarehouses_PUCHSEC006)CHSEC006EXPU
Dimension Diagram2CDC022007F0010
Contact Position IndicationRed ON / Green OFF
I²t Characteristic9AKK107992A5102
Rated Service Short-Circuit Breaking Capacity (Ics)(133 V AC) 15 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu)(133 V AC) 20 kA
Number of Protected Poles1
Lead Time (LeadTime_PUCZABB004)174 day
Warranty Return (NoWarrantyReturn_PUCZABB004)Product under warranty must be returned
Stocked At Warehouses (StockedAtWarehouses_PUCZABB004)CZABB004EXPU
Country of Origin (CountryOfOrigin_PUCZABB004)Czechia
Made To Order (MadeToOrder_PUCZABB004)No
Product Sales Status (ProductSalesStatus_PUCZABB004)Active
Quote Only (QuoteOnly_PUCZABB004)No
Rated Current (In)40 A
Mounting TypeDIN-Rail
Extended Product LifetimeProduct Durability
Connecting CapacityBusbar 10/10 mm²
REACH InformationFalse - does not contain substances > 0.1 mass percentage
RoHS Date20260312
REACH Date20260312
Accessories AvailableYes
Housing MaterialInsulation Group II, RAL 7035
Built-In Depth (t2)69 mm
Overvoltage CategoryIII
Connecting Capacity UL/CSABusbar 18-8 AWG
Electrical Endurance10000 AC cycle
Mechanical Endurance20000 cycle
Screw Terminal TypeFailsafe Bi-directional Cylinder-lift Terminal
Actuator MarkingI / O
Actuator MaterialInsulation Group II, Black, Sealable
Actuator TypeToggle
Operational VoltageMaximum (Incl. Tolerance) 253 V AC
Environmental Conditions28 cycles
Dielectric Test Voltage50 / 60 Hz - 1 min 2 kV
Frequency (f)50 Hz
Input Voltage TypeAC/DC
Offered with Takeback ServicesTake Back for Recycling
Installation Sizeacc. to DIN 43880 1
Rated Short-Circuit Capacity(AC) 6 kA
Certification AgencyEN
Energy Limiting Class3
Tripping CharacteristicC
Pole Net Weight0.125 kg
Power Supply ConnectionArbitrary
Interrupting Rating acc. to UL1077(277 V AC) 6 kA
Reference Ambient Air Temperature30 °C
Standardization BodyEN
Data Sheet, Technical Information9AKK107991A8329
Instructions and Manuals2CDS207104P0002
End Of Life Disassembling Instructions9AKK108468A3132

السعر عند الطلب